TYPE FORM TEMP. RANGE oC (oF) *K-FACTOR/MEAN TEMP.
NOTES
CALCIUM SILICATE Pipe Insulation BlockSegments
to 648.9oC (1200oF) .055 @ 93.3oC [.38 @ 200oF] Strong for its weight,
good workability, water absorbent, non-combustible. See manufacturers'
data for shrinkage factors & application below 121.1oC (250oF).
GLASS CELLULAR Pipe Insulation BlockSegments to 482.2oC (900oF)
.048@ 23.9oC (.33 @ 75oF) .059 @ 93.3oC (.41 @ 200oF) Good
strength, water & vapor resistant, noncombustible, poor abrasion resistance.
For applications over 323.2oC (450oF) see manufacturer specifications.
GLASS FIBER Pipe Insulation Board to 454.4oC (1000oF) to
537.8oC (1000oF) .032 @ 23.9oC (.22 to .23 @ 75oF) .032 @ 93.3oC
(.22 to .38 @ 200oF) Good workability, noncombustible, water absorbent.
GLASS FIBER Blanket to 232.2oC (450oF) .040 @ 23.9oC (.28 to
.38 @ 75oF) General purpose material, many facings available
MINERAL FIBER Pipe InsulationBlock Board Blanket to 648.9oC
(1200oF)to 1037.8oC (1900oF) to 648.9oC (1200oF) to 732.2oC (1350oF)
.040 @ 93.3oC (.28 @ 200oF) .048 @ 93.3oC (.33 @ 200oF).040 @ 93.3oC (.28
to .30 @ 200oF).068 @ 260.0oC (.47 @ 500oF) Good workability, noncombustible.
PERLITE (Expanded) Pipe Insulation Board to 815.6oC (1500oF)
.069 @ 93.3oC (.48 @ 200oF) Good workability, noncombustible.
ELASTOMERIC Pipe Insulation Sheet -40.0oC to
104.4oC (-40oF to 220oF) .040 @ 23.9oC (.28 @ 75oF) Closed
cell, finish not required, good workability.
PHENOLIC (FOAMED) Pipe Insulation -178.9oC to 121.1oC
(-290oF to 250oF) ** Check manufacturers' data sheets for properties.
POLYSTYRENE(Extruded) Pipe Insulation Board -182.8oC to
73.9oC (-297oF to 165oF) .037 @ 23.9oC (.26 @ 75oF) ***
POLYSTYRENE(Expanded) Pipe InsulationBoard -40.0oC
to 73.9oC (-40oF to 165oF) .033 @23.0oC (.23 @ 75oF)
***
POLYURETHANE Pipe Insulation Board -73.3oC to 104.4oC (-100oF
to 220oF) .023 @23.9oC (.16 @ 75oF) ***
POLYISO-CYANURATE Pipe InsulationBoard -182.8oC to
148.9oC (-297oF to 300oF) .026 @ 23.9oC (.18 @ 75oF)
***
POLYETHYLENE Pipe InsulationSheets -67.8oC to 100.0oC
(-90oF to 212oF) .038 @ 23.9oC (.265 @ 75oF) ***
CEMENTS --
NOTES:
1. Temperature range and K-Factor data were compiled from current manufacturer's
published literature. Consult specific manufacturer's data for application
methods.
2. Special attention must be given to high humidity / high temperature
applications, specifically vapor retarder systems.
** See manufacturer's data for K-factor
*** Lightweight, excellent workability, combustible although some are
treated for fire retardancy (check manufacturers' data sheets for properties.)
K-value may change as these materials age.