                                           MATERIALS AND TEMPERATURE
 
 
 
 

TYPE   FORM   TEMP. RANGE oC (oF)  *K-FACTOR/MEAN TEMP. NOTES
CALCIUM SILICATE Pipe Insulation BlockSegments  to 648.9oC (1200oF)to 648.9oC (1200oF)to 648.9oC (1200oF) ** Strong for its weight, good cutting characteristics, some are water absorbent,noncombustible. Some manufacturers limit to 648.9oC (1200oF).  See manufacturers' data for shrinkage factors.
GLASS  CELLULAR Pipe Insulation BlockSegments    to 482.2oC (900oF)   ** Good strength, water & vapor resistant, noncombustible, poor abrasion resistance. For application, see manufacturer  specifications.
GLASS FIBER Pipe Insulation BoardBlanket  to 537.8oC (1000oF) to 537.8oC (1000oF)to 537.8oC (1000oF) ** Good workability, water absorbent, noncombustible.  Check manufacturers' data for specific properties.
MINERAL FIBER  Pipe InsulationBlock BoardBlanket (Felt) to 648.9oC (1200oF) to 1037.8oC (1900oF)to 648.9oC (1200oF) to 732.2oC (1350oF)  ** Good workability, noncombustible. Check manufacturers' data for specific properties.
PERLITE(Expanded) Pipe Covering Insulation Block to 815.6oC (1500oF) ** Good workability,noncombustible, friable. Check manufacturers' data for specific properties.
CERAMIC FIBER (Refractory Fiber)   Blanket Board  to 1482.2oC (2700oF)  to 1648.9oC (3000oF) .115 @ 537.8oC (.80 @ 1000oF).123 @ 537.8oC (.85 @ 1000oF)  Temperature range varies with manufacturer, style and type.
CEMENT  Hydraulic Setting Cement High Temperature Mineral WoolPointing and Finishing Cement (Mineral Fiber or Vermiculite)  to  648.9oC (1200oF)to 1037.8oC (1900oF) to 760.0oC (1400oF) .252 @ 315.6oC (1.75 @ 600oF).099 @ 315.6oC (.69 @ 600oF)**  One coat application -- insulating and finishing. Slow drying, rough texture -- insulating and filling. Used over basic insulation -- Smooth finish, usually 3 to 6 mm (1/8" to 1/4") thick application.
 

Notes:
1. Temperature range and K-Factor data were compiled from current manufacturer's published literature.  Consult specific manufacturer's data for application methods.
2. Special attention must be given to high humidity / high temperature applications, specifically vapor retarder systems.
 
 

** See manufacturers' data for K-factor.